Ground wire size calculator
Rating or setting ahead of the equipment
Only if you upsized the hots, e.g. for voltage drop
The EGC never has to exceed this (250.122(A))
- Table 250.122 sizecopper, row “not exceeding 100 A”
- 8 AWG
- Equipment grounding conductor
- 8 AWG
One EGC serving several circuits in a raceway is sized for the largest overcurrent device in it (250.122(C)). Parallel runs in separate raceways get a full-size EGC in each (250.122(F)). Motor circuits on an instantaneous-trip breaker size from a dual-element fuse rating instead (250.122(D)).
Nothing typed leaves the browser; the inputs live only in the page address.
Two different grounds, two different tables. The equipment grounding conductor (EGC) that runs with a circuit is sized from the breaker or fuse ahead of it, by Table 250.122. The grounding electrode conductor (GEC) that connects the service to the rods, the water pipe or the footing steel is sized from the service-entrance conductors, by Table 250.66. Pick which one you are sizing; the answer names the table row it came from. If you went up a size on the hots for voltage drop, enter both sizes and the EGC grows in proportion, as 250.122(B) requires.
Worked examples
- 100 A subpanel feeder, copper EGC
- Table 250.122, row “not exceeding 100 A”: 8 AWG copper, or 6 AWG aluminum. The same 8 AWG serves 61 A to 100 A; at 101 A the row changes to 6 AWG. Open this run
- 20 A circuit, hots upsized from 12 to 10 AWG for a long run
- Table value 12 AWG. 250.122(B): 10,380 ÷ 6,530 cmil = × 1.590, so the EGC needs 6,530 × 1.590 = 10,380 cmil: 10 AWG. In practice an upsized NM or MC cable already carries the larger ground; with single conductors in conduit it is easy to miss. Open this run
- 200 A feeder, 3/0 copper upsized to 250 kcmil
- Table 250.122 at 200 A: 6 AWG copper (26,240 cmil). 250,000 ÷ 167,800 = × 1.490, so 39,094 cmil is needed and 6 AWG is short; the next size, 4 AWG (41,740 cmil), is the answer. Open this run
- 200 A service on 2/0 copper, GEC to the water pipe and rods
- Table 250.66, row “2/0 or 3/0”: 4 AWG copper. If the conductor runs only to ground rods, 250.66(A) caps it at 6 AWG copper; only to a concrete-encased electrode, 250.66(B) caps it at 4 AWG copper. Open this run
- Three parallel sets of 500 kcmil copper
- Note 1 sums the areas: 3 × 500 = 1,500 kcmil, which is “over 1100”. GEC: 3/0 copper or 250 kcmil aluminum, unless it runs only to rods (6 AWG copper). Open this run
How it is worked out
EGC: take the first Table 250.122 row whose ampere value is not less than the rating or setting of the overcurrent device ahead of the equipment, and read the copper or aluminum column. The table is a minimum; 250.122(A) never requires the EGC to be larger than the circuit conductors.
250.122(B): if the ungrounded conductors were increased above the minimum size that has the ampacity, the EGC is multiplied by the same circular-mil ratio (installed area ÷ minimum area, from Chapter 9 Table 8) and the next standard size at or above the result is used, still no larger than the circuit conductors.
GEC: find the area of the largest ungrounded service-entrance conductor (for parallel sets, the sum of one conductor from each set, Note 1), locate its Table 250.66 row in the copper or aluminum column, and read the GEC size in the material you are using.
250.66(A) to (C) set ceilings when the GEC runs only to one kind of electrode: 6 AWG copper or 4 AWG aluminum to rods, pipes or plates; 4 AWG copper to a concrete-encased electrode; the ring conductor’s size to a ground ring.
The figures behind it
- NEC Table 250.122, Minimum Size Equipment Grounding Conductors
- 15 A to 6000 A, copper and aluminum or copper-clad aluminum columns. Read from the NFPA-typeset 2017 text and cross-checked cell by cell against a reproduction headed for NEC 2020 through 2026; UpCodes’ 2020 and 2023 entries confirm the 15 A and 6000 A end rows. Checked 2026-10-11. Source
- NEC Table 250.66, Grounding Electrode Conductor for AC Systems
- Seven rows from “2 or smaller” to “over 1100” (copper service conductors) and “1/0 or smaller” to “over 1750” (aluminum). Same sources and cross-check as Table 250.122. Row bounds are converted to circular mils with Chapter 9 Table 8 so parallel sets can be summed. Source
- 250.122(A), (B), (C), (D), (F) and 250.66(A), (B), (C)
- Paraphrased from the 2017 text. The 2020 and later wording of 250.122(B) could not be read from an open NFPA-typeset copy; the arithmetic here is the proportional circular-mil increase the rule has required since the 2017 text. Check the edition your jurisdiction enforces. Source
- NEC Chapter 9 Table 8, Conductor Properties
- Circular-mil areas and DC resistance at 75 °C (ohm/kFT) for 18 AWG to 1000 kcmil, copper uncoated and aluminum. Read from the NFPA-typeset 2017 text and cross-checked cell by cell with a 2014 reproduction; the table is unchanged since at least 2005, so the 2023 values are inferred from that history rather than read from a 2023 copy. Checked 2026-09-05. Source
Table 250.122: equipment grounding conductor by breaker size
| OCPD not exceeding | Covers | Copper | Aluminum or copper-clad aluminum |
|---|---|---|---|
| 15 A | up to 15 A | 14 AWG | 12 AWG |
| 20 A | 16–20 A | 12 AWG | 10 AWG |
| 60 A | 21–60 A | 10 AWG | 8 AWG |
| 100 A | 61–100 A | 8 AWG | 6 AWG |
| 200 A | 101–200 A | 6 AWG | 4 AWG |
| 300 A | 201–300 A | 4 AWG | 2 AWG |
| 400 A | 301–400 A | 3 AWG | 1 AWG |
| 500 A | 401–500 A | 2 AWG | 1/0 AWG |
| 600 A | 501–600 A | 1 AWG | 2/0 AWG |
| 800 A | 601–800 A | 1/0 AWG | 3/0 AWG |
| 1,000 A | 801–1,000 A | 2/0 AWG | 4/0 AWG |
| 1,200 A | 1,001–1,200 A | 3/0 AWG | 250 kcmil |
| 1,600 A | 1,201–1,600 A | 4/0 AWG | 350 kcmil |
| 2,000 A | 1,601–2,000 A | 250 kcmil | 400 kcmil |
| 2,500 A | 2,001–2,500 A | 350 kcmil | 600 kcmil |
| 3,000 A | 2,501–3,000 A | 400 kcmil | 600 kcmil |
| 4,000 A | 3,001–4,000 A | 500 kcmil | 750 kcmil |
| 5,000 A | 4,001–5,000 A | 700 kcmil | 1200 kcmil |
| 6,000 A | 5,001–6,000 A | 800 kcmil | 1200 kcmil |
Table 250.66: grounding electrode conductor by service conductor size
| Service conductor, copper | Service conductor, aluminum | GEC, copper | GEC, aluminum |
|---|---|---|---|
| 2 or smaller | 1/0 or smaller | 8 AWG | 6 AWG |
| 1 or 1/0 | 2/0 or 3/0 | 6 AWG | 4 AWG |
| 2/0 or 3/0 | 4/0 or 250 | 4 AWG | 2 AWG |
| Over 3/0 through 350 | Over 250 through 500 | 2 AWG | 1/0 AWG |
| Over 350 through 600 | Over 500 through 900 | 1/0 AWG | 3/0 AWG |
| Over 600 through 1100 | Over 900 through 1750 | 2/0 AWG | 4/0 AWG |
| Over 1100 | Over 1750 | 3/0 AWG | 250 kcmil |
Questions people ask
- What size ground wire for a 100 amp subpanel?
- 8 AWG copper or 6 AWG aluminum for the equipment grounding conductor in the feeder (Table 250.122, row 100 A). A separate building also needs its own grounding electrode system; that GEC is sized from the feeder conductors by Table 250.66.
- What size ground wire for a 200 amp service?
- At the service it is the grounding electrode conductor, sized by Table 250.66 from the service conductors: 4 AWG copper for 2/0 or 3/0 copper (or 4/0 or 250 aluminum) service conductors, and 6 AWG copper if it runs only to ground rods. A 200 A feeder to a subpanel carries a 6 AWG copper or 4 AWG aluminum EGC by Table 250.122.
- What size ground for a 30, 40, 50 or 60 amp circuit?
- 10 AWG copper for all four: Table 250.122 has one row covering 21 A to 60 A. Aluminum: 8 AWG. 15 A takes 14 AWG copper and 20 A takes 12 AWG copper.
- Is the ground wire the same size as the hot wires?
- Up to 20 A it usually is, because the table matches the circuit conductors. Above that it is smaller: a 100 A feeder on 3 AWG copper carries an 8 AWG copper EGC. It is never required to be larger than the circuit conductors (250.122(A)).
- If I upsize the wire for voltage drop, do I upsize the ground?
- Yes, for wire-type EGCs. 250.122(B) requires the EGC to grow in proportion to the circular-mil increase of the ungrounded conductors. Going from 12 to 10 AWG on a 20 A circuit takes the EGC from 12 to 10 AWG too.
- What is the difference between an EGC and a GEC?
- The equipment grounding conductor runs with the circuit and gives fault current a path back to the source so the breaker trips; it is sized by the breaker (Table 250.122). The grounding electrode conductor connects the system to the earth through rods, pipe or footing steel; it is sized by the service conductors (Table 250.66). 250.121 says an EGC is not to be used as a GEC, with one exception for a wire that meets the rules for both.
- Does the ground wire count in conduit fill and box fill?
- Yes. Chapter 9 Note 3 counts equipment grounding conductors in conduit fill at their actual dimensions, and 314.16(B)(5) counts all equipment grounding conductors in a box as one volume allowance (the 2020 and later editions add a quarter allowance for each beyond four). They do not count toward the ampacity adjustment for current-carrying conductors.
Embed this calculator
Paste this anywhere HTML is allowed. Free; keep the credit link.
<iframe src="https://necwire.com/embed/ground-wire-size-calculator" width="100%" height="760" loading="lazy" title="Ground wire size calculator"></iframe> <p><a href="https://necwire.com/ground-wire-size-calculator">Ground wire size calculator</a> by NECwire</p>