NECwire

Ground wire size calculator

Equipment grounding conductor8AWGTABLE 250.122copper, overcurrent device 100 A: row “not exceeding 100 A” · NEC 2017 Table 250.122, cross-checked against a NEC 2020-2026 reproduction
What are you sizing?

Rating or setting ahead of the equipment

EGC material

Only if you upsized the hots, e.g. for voltage drop

The EGC never has to exceed this (250.122(A))

Table 250.122 sizecopper, row “not exceeding 100 A”
8 AWG
Equipment grounding conductor
8 AWG

One EGC serving several circuits in a raceway is sized for the largest overcurrent device in it (250.122(C)). Parallel runs in separate raceways get a full-size EGC in each (250.122(F)). Motor circuits on an instantaneous-trip breaker size from a dual-element fuse rating instead (250.122(D)).

Nothing typed leaves the browser; the inputs live only in the page address.

Two different grounds, two different tables. The equipment grounding conductor (EGC) that runs with a circuit is sized from the breaker or fuse ahead of it, by Table 250.122. The grounding electrode conductor (GEC) that connects the service to the rods, the water pipe or the footing steel is sized from the service-entrance conductors, by Table 250.66. Pick which one you are sizing; the answer names the table row it came from. If you went up a size on the hots for voltage drop, enter both sizes and the EGC grows in proportion, as 250.122(B) requires.

Worked examples

100 A subpanel feeder, copper EGC
Table 250.122, row “not exceeding 100 A”: 8 AWG copper, or 6 AWG aluminum. The same 8 AWG serves 61 A to 100 A; at 101 A the row changes to 6 AWG. Open this run
20 A circuit, hots upsized from 12 to 10 AWG for a long run
Table value 12 AWG. 250.122(B): 10,380 ÷ 6,530 cmil = × 1.590, so the EGC needs 6,530 × 1.590 = 10,380 cmil: 10 AWG. In practice an upsized NM or MC cable already carries the larger ground; with single conductors in conduit it is easy to miss. Open this run
200 A feeder, 3/0 copper upsized to 250 kcmil
Table 250.122 at 200 A: 6 AWG copper (26,240 cmil). 250,000 ÷ 167,800 = × 1.490, so 39,094 cmil is needed and 6 AWG is short; the next size, 4 AWG (41,740 cmil), is the answer. Open this run
200 A service on 2/0 copper, GEC to the water pipe and rods
Table 250.66, row “2/0 or 3/0”: 4 AWG copper. If the conductor runs only to ground rods, 250.66(A) caps it at 6 AWG copper; only to a concrete-encased electrode, 250.66(B) caps it at 4 AWG copper. Open this run
Three parallel sets of 500 kcmil copper
Note 1 sums the areas: 3 × 500 = 1,500 kcmil, which is “over 1100”. GEC: 3/0 copper or 250 kcmil aluminum, unless it runs only to rods (6 AWG copper). Open this run

How it is worked out

EGC: take the first Table 250.122 row whose ampere value is not less than the rating or setting of the overcurrent device ahead of the equipment, and read the copper or aluminum column. The table is a minimum; 250.122(A) never requires the EGC to be larger than the circuit conductors.

250.122(B): if the ungrounded conductors were increased above the minimum size that has the ampacity, the EGC is multiplied by the same circular-mil ratio (installed area ÷ minimum area, from Chapter 9 Table 8) and the next standard size at or above the result is used, still no larger than the circuit conductors.

GEC: find the area of the largest ungrounded service-entrance conductor (for parallel sets, the sum of one conductor from each set, Note 1), locate its Table 250.66 row in the copper or aluminum column, and read the GEC size in the material you are using.

250.66(A) to (C) set ceilings when the GEC runs only to one kind of electrode: 6 AWG copper or 4 AWG aluminum to rods, pipes or plates; 4 AWG copper to a concrete-encased electrode; the ring conductor’s size to a ground ring.

The figures behind it

NEC Table 250.122, Minimum Size Equipment Grounding Conductors
15 A to 6000 A, copper and aluminum or copper-clad aluminum columns. Read from the NFPA-typeset 2017 text and cross-checked cell by cell against a reproduction headed for NEC 2020 through 2026; UpCodes’ 2020 and 2023 entries confirm the 15 A and 6000 A end rows. Checked 2026-10-11. Source
NEC Table 250.66, Grounding Electrode Conductor for AC Systems
Seven rows from “2 or smaller” to “over 1100” (copper service conductors) and “1/0 or smaller” to “over 1750” (aluminum). Same sources and cross-check as Table 250.122. Row bounds are converted to circular mils with Chapter 9 Table 8 so parallel sets can be summed. Source
250.122(A), (B), (C), (D), (F) and 250.66(A), (B), (C)
Paraphrased from the 2017 text. The 2020 and later wording of 250.122(B) could not be read from an open NFPA-typeset copy; the arithmetic here is the proportional circular-mil increase the rule has required since the 2017 text. Check the edition your jurisdiction enforces. Source
NEC Chapter 9 Table 8, Conductor Properties
Circular-mil areas and DC resistance at 75 °C (ohm/kFT) for 18 AWG to 1000 kcmil, copper uncoated and aluminum. Read from the NFPA-typeset 2017 text and cross-checked cell by cell with a 2014 reproduction; the table is unchanged since at least 2005, so the 2023 values are inferred from that history rather than read from a 2023 copy. Checked 2026-09-05. Source

Table 250.122: equipment grounding conductor by breaker size

Read the row whose ampere value is not less than the breaker or fuse ahead of the equipment. The range column is the span of device ratings each row covers.
OCPD not exceedingCoversCopperAluminum or copper-clad aluminum
15 Aup to 15 A14 AWG12 AWG
20 A16–20 A12 AWG10 AWG
60 A21–60 A10 AWG8 AWG
100 A61–100 A8 AWG6 AWG
200 A101–200 A6 AWG4 AWG
300 A201–300 A4 AWG2 AWG
400 A301–400 A3 AWG1 AWG
500 A401–500 A2 AWG1/0 AWG
600 A501–600 A1 AWG2/0 AWG
800 A601–800 A1/0 AWG3/0 AWG
1,000 A801–1,000 A2/0 AWG4/0 AWG
1,200 A1,001–1,200 A3/0 AWG250 kcmil
1,600 A1,201–1,600 A4/0 AWG350 kcmil
2,000 A1,601–2,000 A250 kcmil400 kcmil
2,500 A2,001–2,500 A350 kcmil600 kcmil
3,000 A2,501–3,000 A400 kcmil600 kcmil
4,000 A3,001–4,000 A500 kcmil750 kcmil
5,000 A4,001–5,000 A700 kcmil1200 kcmil
6,000 A5,001–6,000 A800 kcmil1200 kcmil
250.122(A): a wire-type equipment grounding conductor shall not be smaller than Table 250.122, but is never required to be larger than the circuit conductors supplying the equipment. The printed table carries a note that the EGC must be larger where needed to clear a fault (250.4(A)(5) or (B)(4)), and an asterisk sending aluminum to the installation limits of 250.120. Source: NEC 2017 (NFPA 70-2017) Tables 250.66 and 250.122; identical cell for cell to a reproduction headed NEC 2020-2026. 2017 text, cross-check.

Table 250.66: grounding electrode conductor by service conductor size

Find the largest ungrounded service-entrance conductor in the column for its material, then read the GEC in the material you will use. For parallel sets, add the areas of one conductor from each set first.
Service conductor, copperService conductor, aluminumGEC, copperGEC, aluminum
2 or smaller1/0 or smaller8 AWG6 AWG
1 or 1/02/0 or 3/06 AWG4 AWG
2/0 or 3/04/0 or 2504 AWG2 AWG
Over 3/0 through 350Over 250 through 5002 AWG1/0 AWG
Over 350 through 600Over 500 through 9001/0 AWG3/0 AWG
Over 600 through 1100Over 900 through 17502/0 AWG4/0 AWG
Over 1100Over 17503/0 AWG250 kcmil
Table 250.66 Note 1: with multiple sets of service-entrance conductors, the equivalent size of the largest one is the largest sum of the areas of the corresponding conductors of each set. 250.66(A): a grounding electrode conductor to rod, pipe or plate electrodes only, not extending to other electrode types, need not be larger than 6 AWG copper or 4 AWG aluminum. 250.66(B): to concrete-encased electrodes only, it need not be larger than 4 AWG copper. 250.66(C): to a ground ring only, it need not be larger than the conductor used for the ring.

Questions people ask

What size ground wire for a 100 amp subpanel?
8 AWG copper or 6 AWG aluminum for the equipment grounding conductor in the feeder (Table 250.122, row 100 A). A separate building also needs its own grounding electrode system; that GEC is sized from the feeder conductors by Table 250.66.
What size ground wire for a 200 amp service?
At the service it is the grounding electrode conductor, sized by Table 250.66 from the service conductors: 4 AWG copper for 2/0 or 3/0 copper (or 4/0 or 250 aluminum) service conductors, and 6 AWG copper if it runs only to ground rods. A 200 A feeder to a subpanel carries a 6 AWG copper or 4 AWG aluminum EGC by Table 250.122.
What size ground for a 30, 40, 50 or 60 amp circuit?
10 AWG copper for all four: Table 250.122 has one row covering 21 A to 60 A. Aluminum: 8 AWG. 15 A takes 14 AWG copper and 20 A takes 12 AWG copper.
Is the ground wire the same size as the hot wires?
Up to 20 A it usually is, because the table matches the circuit conductors. Above that it is smaller: a 100 A feeder on 3 AWG copper carries an 8 AWG copper EGC. It is never required to be larger than the circuit conductors (250.122(A)).
If I upsize the wire for voltage drop, do I upsize the ground?
Yes, for wire-type EGCs. 250.122(B) requires the EGC to grow in proportion to the circular-mil increase of the ungrounded conductors. Going from 12 to 10 AWG on a 20 A circuit takes the EGC from 12 to 10 AWG too.
What is the difference between an EGC and a GEC?
The equipment grounding conductor runs with the circuit and gives fault current a path back to the source so the breaker trips; it is sized by the breaker (Table 250.122). The grounding electrode conductor connects the system to the earth through rods, pipe or footing steel; it is sized by the service conductors (Table 250.66). 250.121 says an EGC is not to be used as a GEC, with one exception for a wire that meets the rules for both.
Does the ground wire count in conduit fill and box fill?
Yes. Chapter 9 Note 3 counts equipment grounding conductors in conduit fill at their actual dimensions, and 314.16(B)(5) counts all equipment grounding conductors in a box as one volume allowance (the 2020 and later editions add a quarter allowance for each beyond four). They do not count toward the ampacity adjustment for current-carrying conductors.

Embed this calculator

Paste this anywhere HTML is allowed. Free; keep the credit link.

<iframe src="https://necwire.com/embed/ground-wire-size-calculator" width="100%" height="760" loading="lazy" title="Ground wire size calculator"></iframe>
<p><a href="https://necwire.com/ground-wire-size-calculator">Ground wire size calculator</a> by NECwire</p>