kVA calculator

Apparent power · single-phase24.00kVAkVA = V × I ÷ 1000240 V × 100 A
Given
Phase

Line-to-neutral or 240

Per line

0.8 is the usual assumption for mixed motor loads

Real powerkVA × PF
19.20 kW
Reactive power√(kVA² − kW²)
14.40 kvar
Line currentkVA × 1000 ÷ 240 V
100.0 A
Next common transformer ratingcommon dry-type catalogue sizes, not a code table
25 kVA

Transformers and generators are rated in kVA because heating depends on current, not on the power factor of what is plugged in. Sizing a transformer also needs the load calculation of Article 220 and the 450.3 protection table; this page is the arithmetic only.

Nothing typed leaves the browser; the inputs live only in the page address.

Transformers, generators and services are rated in kilovolt-amperes because heating follows current, not the power factor of the load. Give volts and amps, or kilowatts and a power factor, and read the kVA, the real and reactive power, the line current and the next common transformer size. Sizing a transformer also needs the Article 220 load calculation and the 450.3 protection table; this is the arithmetic.

Worked examples

240 V, 100 A single-phase
24 kVA. At PF 0.8 that is 19.2 kW and 14.4 kvar; a 25 kVA transformer is the next standard size. Open this run
480 V, 100 A three-phase
√3 × 480 × 100 ÷ 1000 = 83.1 kVA; a 112.5 kVA three-phase transformer is the next common rating. Open this run
100 kW at PF 0.8
125 kVA and 75 kvar. Improving the power factor to 0.95 brings the same 100 kW down to 105 kVA. Open this run
Generator: 7.5 kW at PF 0.8, 240 V
9.4 kVA and 39 A. Most portable generators are rated in watts at PF 1; standby units in kW at 0.8. Open this run

How it is worked out

kVA = V × I ÷ 1000 (single-phase) or √3 × V × I ÷ 1000 (three-phase, V line-to-line). kVA = kW ÷ PF. kW = kVA × PF. kvar = √(kVA² − kW²). I = kVA × 1000 ÷ V or ÷ (√3 × V).

The transformer list (1 to 1000 kVA) is the common dry-type catalogue sizes, not a code table.

The figures behind it

Apparent power
S = V × I, P = S × PF, Q = √(S² − P²); arithmetic, no table.

Questions people ask

How many amps is a 25 kVA transformer?
Single-phase at 240 V: 25,000 ÷ 240 = 104 A. Three-phase at 208 V: 25,000 ÷ (√3 × 208) = 69 A per line.
kVA or kW for a generator?
Generators carry both: the kVA is the alternator’s current limit, the kW the engine’s. At PF 0.8 a 10 kVA set delivers 8 kW. Size on the larger of the load’s kVA and kW needs.

Embed this calculator

Paste this anywhere HTML is allowed. Free; keep the credit link.

<iframe src="https://necwire.com/embed/kva-calculator" width="100%" height="760" loading="lazy" title="kVA calculator"></iframe>
<p><a href="https://necwire.com/kva-calculator">kVA calculator</a> by NECwire</p>