NECwire

Motor FLA calculator

Full-load current · Table 430.25014.0ATABLE VALUE10 hp, 460 V three-phase induction; use this table value, not the nameplate, for conductors and OCPD (430.6(A)(1)) · NEC 2017, identical to 2011
Phase
Branch-circuit conductors, minimum ampacity430.22: 125 % of the table FLC
17.5 A
Inverse-time breaker, max 250 %Table 430.52; next standard size 35 A permitted by 430.52(C)(1) Ex. 1 where the value does not match a standard rating
35.0 A
Dual-element time-delay fuse, max 175 %next standard 25 A
24.5 A
Nontime-delay fuse, max 300 %
42.0 A
Instantaneous-trip breaker, max 1100 %listed combination starters only
154 A

Overload protection (430.32) uses the nameplate current, not the table; typically 115 % or 125 % by service factor and temperature rise. Multi-motor circuits, Design B exceptions and the 430.52(C)(1) exceptions are the electrician’s call.

Nothing typed leaves the browser; the inputs live only in the page address.

Motor branch circuits are sized from the NEC tables, not the nameplate: 430.6(A)(1) sends you to Table 430.248 for single-phase and 430.250 for three-phase motors. Pick the horsepower and voltage and read the full-load current, the conductor ampacity at 125 % (430.22), and the maximum overcurrent device by type from Table 430.52. Overload protection is the exception: it uses the nameplate (430.32).

Worked examples

10 hp three-phase at 460 V
Table 430.250: 14 A. Conductors 17.5 A (12 AWG at 75 °C carries 25 A). Inverse-time breaker up to 250 % = 35 A; dual-element fuse up to 175 % = 24.5 A, next standard 25 A. Open this run
1 hp single-phase at 115 V
Table 430.248: 16 A. Conductors 20 A (12 AWG); breaker up to 40 A, dual-element fuse up to 28 A, next standard 30 A. Open this run
25 hp three-phase at 208 V
74.8 A. Conductors 93.5 A (3 AWG at 75 °C, 100 A); breaker up to 187 A, so a 175 A device, or 200 A by the 430.52(C)(1) Exception 1 next-size rule. Open this run
5 hp single-phase at 230 V
28 A. Conductors 35 A (8 AWG at 75 °C, 50 A; 10 AWG is 35 A but 240.4(D) matters only for the OCPD); breaker up to 70 A. Open this run

How it is worked out

FLC is read from Table 430.248 (single-phase, 1/6 to 10 hp at 115, 200, 208, 230 V) or Table 430.250 (three-phase induction, ½ to 500 hp at 115 to 2300 V). Where the table prints a dash the page says so rather than interpolating.

Conductors: ampacity ≥ 1.25 × FLC (430.22). Branch-circuit short-circuit and ground-fault protection: ≤ FLC × the Table 430.52 percentage for the device type (nontime-delay fuse 300 %, dual-element fuse 175 %, instantaneous-trip breaker 800 % or 1100 % for Design B, inverse-time breaker 250 %), with the next standard size permitted by 430.52(C)(1) Exception 1 where the product is not a standard rating.

The figures behind it

NEC Tables 430.248 and 430.250
Full-load currents, 2017 text verbatim, cross-checked with the 2011 NECA-IBEW reproduction: identical. Synchronous-motor columns and the 90 / 80 % power-factor multipliers are in the data but not exposed in the picker. Source
NEC 430.22 and Table 430.52
125 % conductor rule and the maximum OCPD percentages by motor and device type, 2017 text; standard ratings from 240.6(A). Source
Edition note
No open 2020 or 2023 copy was reachable; the 2011 and 2017 values match and “unchanged in 2023” is inferred. Source

Table 430.248: single-phase motor full-load current

Amperes, single-phase AC motors. The following values of full-load currents are for motors running at usual speeds and motors with normal torque characteristics. The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120 and 220 to 240 volts.
hp115 V200 V208 V230 V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.143.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88
1-1/22011.51110
22413.813.212
33419.618.717
55632.230.828
7-1/280464440
1010057.55550
Source: NEC 2017 (NFPA 70-2017) Tables 430.248, 430.250, 430.52; identical to 2011. Use these values, not the nameplate, for conductors, switches and short-circuit protection (430.6(A)(1)).

Table 430.250: three-phase motor full-load current

Amperes, induction-type squirrel cage and wound rotor, then synchronous at unity power factor. The following values of full-load currents are typical for motors running at speeds usual for belted motors and motors with normal torque characteristics. The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120, 220 to 240, 440 to 480, and 550 to 600 volts.
hp115 V200 V208 V230 V460 V575 V2300 VSync. 230 VSync. 460 VSync. 575 VSync. 2300 V
1/24.42.52.42.21.10.9—————
3/46.43.73.53.21.61.3—————
18.44.84.64.22.11.7—————
1-1/2126.96.6632.4—————
213.67.87.56.83.42.7—————
3—1110.69.64.83.9—————
5—17.516.715.27.66.1—————
7-1/2—25.324.222119—————
10—32.230.8281411—————
15—48.346.2422117—————
20—62.159.4542722—————
25—78.274.8683427—532621—
30—9288804032—633226—
40—1201141045241—834133—
50—1501431306552—1045242—
60—177169154776216123614912
75—221211192967720155786215
100—28527324812499262021018120
125—3593433121561253125312610125
150—4143963601801443730215112130
200—5525284802401924940020116140
250————30224260————
300————36128972————
350————41433683————
400————47738295————
450————515412103————
500————590472118————
For 90 and 80 percent power factor, the [synchronous] figures shall be multiplied by 1.1 and 1.25, respectively. A dash means the table lists no value. Source: NEC 2017 (NFPA 70-2017) Tables 430.248, 430.250, 430.52; identical to 2011.

Questions people ask

Why not use the nameplate amps?
430.6(A)(1) requires the table values for conductor, switch and overcurrent sizing so that a replacement motor of the same horsepower fits the circuit. The nameplate current is used only for overload protection (430.32).
What breaker for a 10 hp 460 V motor?
FLC 14 A; inverse-time breaker up to 250 % = 35 A. A 35 A breaker is a standard size; if the motor will not start, 430.52(C)(1) Exception 2 allows up to 400 % for currents of 100 A or less.
The table has no 3 hp at 115 V single-phase; why?
Table 430.248 stops at 2 hp for 115 V (24 A); larger motors are not built for 115 V. The page prints “not listed” rather than a made-up figure.